ITC VA-2240WM 2 Zones Voice Evacuation Controller
* Built-in 240W high-efficiency digital power amplifier, integrated 2 power A + B independent dual-speaker loop zone output, each zone has independent LED indicator, independent output control buttons and volume adjustment.
* 4 audio balanced input interfaces for playing any audio source in the zones
* Local emergency PTT microphone input and emergency voice can be configured by PC software to be played in specific zone.
* Automatically detect the working status of each zone loop (fault, normal)
* The 4-channel trigger input/output port can trigger the emergency voice preset by the PC software to the specified zone or the corresponding external power source to the corresponding event warning.
* Support third-party emergency audio input (user-defined emergency audio source)
* Integrated independent EVAC/ALERT voice information player.
* There are online interface for the remote paging microphone and fireman microphone. The connection between each paging station uses standard RJ-45 network port and standard CAT-5 network cable. The voice transmission uses balanced transmission mode for long-distance transmission.
* Controller online interface can be connected to the slave unit, it uses standard RJ-45 network port and standard CAT-5 network cable.
* 1 channel TCP/IP communication interface, supports visual interface operation based on Window platform, and the system status can be automatically synchronized.
* Support DC24V battery backup power supply.
* With power amplifier monitoring function.
* Support PTT recording function, no external equipment required.
* With System fault output, emergency dry contact output and dry contact reset input for emergency statusThe zone output has three-wire and four-wire over-ridding adjustment functions.
* With IP address reset function and impedance calibration function.
* The master-slave unit is integrated, and the device can be used as a controller or a slave unit by setting DIP address, and the maximum of 19 slaves can be simultaneously online.
The system can extend the number of the zones by slave units, it support 40 zones maximum.
Specifications
Model
VA-2240WM
Voltage
~ 220V±20%, 50/60Hz
Fuse specifications
2A slow breaking type
MIC input
Sensitivity
±2.5mV
Frequency response
200Hz~10KHz
Input impedance
1KΩ
Signal to noise ratio >65dB
>65dB
Balanced line input
Sensitivity
±385mV
Frequency response
80Hz~16KHz
Input impedance
10KΩ
Signal to noise ratio
>70dB
RS485 interface
Slave RS485 interface
Supports the highest baud rate of 38400bps
Support up to 19 expansion machines
CAN interface
Remote MIC console CAN interface
Baud rate 50Kbps
Supports up to 28 remote Microphone and 4 Fireman Remote Microphone
Trigger mode
short circuit trigger and level trigger
Output mode
relay short circuit output
Size (L×W×H)
570×440×186mm
Net weight
17.6Kg
Installation
Wall Mounted
Color
Fireman's Red
Operating temperature
+5℃~ +40℃
Storage temperature
-20℃~ +70℃
Relative temperature
<95%